-16AWG

Shielded VNTC - UL Type TC or TC-ER, 600 V, 90°C dry and 75°C wet rated - LEAD FREE
Multiconductor 16 AWG Type TFN
Insulation Thickness:  15 mils  / 0.38mm PVC, 4 mils / 0.10mm Nylon Covering
Drain Wire:  18 AWG (7w) Tinned Copper Bend Radius:  5 x overall diameter installed / 8 x overall diameter during installation.

Notes:
• Dimensions and weights shown are nominal values.  They are subject to standard industry tolerances.
• Cables with different conductor counts are bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in 
accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Article 336.80, and Table 402.5 "Allowable Ampacity
for Fixture Wires" at an ambient temperature of 30°C (with no load diversity).  Ampacity for 
cables having more than three conductors have been derated as stated in NEC Article 392.80(A),
using the derating factors of NEC Table 310.15(B)(3)(a).  For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different 
conductor temperature ratings see NEC Table 310.15(B)(16).
• Refer to NEC Article 240.4(D) for overcurrent protection requirements.

Colors

Conductor Identification:
• Per ICEA S-73-532-E3.4 Method 4
Conductors are black and numbered
• Per ICEA S-73-532-E3.1 Method 1 and Table E2 (formerly K2)
Colored Insulation (with stripe for 7th conductor and beyond)

Scroll to add product to your quote.

Cole Number Size AWG No. Of Cond. JKT Wall NOM O.D. D.C. Volts AMPS (1) Weight LBS/MFT Color Quantity Add
16-0207 16 2 45 .298 600V 8 51
16-0208 16 3 45 .314 600V 8 67
16-0209 16 4 45 .339 600V 6.4 80
16-0210 16 5 45 .368 600V 6.4 96
16-0211 16 6 45 .398 600V 6.4 165
16-0213 16 7 45 .398 600V 5.6 120
16-0214 16 8 45 .435 600V 5.6 136
16-0215 16 9 45 .467 600V 5.6 149
16-0216 16 12 60 .549 600V 4 187
16-0217 16 19 60 .634 600V 4 301
16-0218 16 37 80 .885 600V 3.2 568