10AWG (1)

XLP/PVC Tray Cable Unshielded Multiconductor Tray Cable 10 AWG
Multiconductor 10 AWG Type XHHW-2
Insulation Thickness:  30 mils /0 .76 mm
Conductor: Bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8.
Insulation: Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-95-658
for XLPE insulation as standard. Rated VW-1
Assembly: Conductors are cabled in concentric layers with interstices filled with suitable fillers, as required.  Ground wires, are sized as required by UL 1277
(refer to the applicable product tables for the standard provided).  Cable has an insulated green ground wire. 
A binder tape of synthetic material assembles the core in a tight circular configuration.
Jacket: UL listed sunlight and moisture resistant, sequentially length marked, black polyvinyl chloride (PVC) material meeting the requirements of UL 1277.

Bend Radius: 5 x overall diameter installed
8 x overall diameter during installation pull-in.
       
Notes:
• Dimensions and weights shown are nominal values, subject to standard industry tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC 2008 and
NEC 2011 Article 336.10(7).
• Ampacities are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in raceway
or direct buried at 30°C ambient temperature and 90°C rated conductors. Ampacities for cables having more than three
conductors have been derated per NEC 2008 Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC 2008 Table B.310.11 or NEC 2011 Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC
2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG
copper after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this
may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G).
(1) Where the 4th conductor is the neutral of a balanced 3 phase system.

Scroll to add product to your quote.

Cole Number Size AWG No. Of Cond. JKT Wall NOM O.D. D.C. Volts AMPS (1) Weight LBS/MFT Color Quantity Add
16-0428 10 2 45 .470 600V 40 128
16-0429 10 3 45 .495 600V 40 174
16-0430 10 4 45 .545 600V 32/40 223
16-0431 10 5 60 .630 600V 32 290
16-0432 10 7 60 .685 600V 28 382
16-0433 10 9 60 .800 600V 28 479
16-0434 10 12 80 .935 600V 20 626
16-0435 10 15 80 1.010 600V 20 760
16-0436 10 19 80 1.070 600V 20 900