4 Conductor

Unshielded VNTC - 4 Conductor w/Ground, UL Type TC-ER, 600 V, 90°C dry and wet rated - RoHS Compliant

Bend Radius:  5 x overall diameter installed (up to 2.0") / 6 x overall diameter installed (over 2.0") 
8 x overall diameter during installation pull-in.

Notes:
• Dimensions and weights shown are nominal values, subject to standard industry tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct
buried at 30°C ambient temperature and 90°C rated conductors. Ampacities for cables having 
more than three conductors have been derated per NEC Table 310.15(B)(3)(a).
•For correction factors for different ambient temperatures and ampacities at different conductor 
temperature ratings see NEC Table 310.15(B)(16).
(1) Where the 4th conductor is the neutral of a balanced 3 phase system.
• Control conductors are color coded E-2 
• Power conductors are black with numbers - M4 
• Fillers where applicable.

Scroll to add product to your quote.

Cole Number Size AWG No. Of Cond. JKT Wall NOM O.D. Ground AWG D.C. Volts AMPS (1) Weight LBS/MFT Color Quantity Add
16-0351 8 4 60 .661 10 600V 44 353
16-0353 6 4 60 .796 8 600V 60 516
16-0355 4 4 80 .957 8 600V 76 804
16-0357 2 4 80 1.102 6 600V 104 1108
16-0359 1 4 80 1.247 6 600V 120 1519
16-0361 1/0 4 80 1.314 6 600V 136 1811
16-0363 2/0 4 80 1.452 6 600V 156 2288
13-0365 3/0 4 80 1.575 4 600V 180 2756
13-0367 4/0 4 110 1.768 4 600V 208 3437
16-0369 250 4 110 1.937 4 600V 232 4046
13-0371 350 4 110 2.180 3 600V 280 5480
16-0373 500 4 110 2.494 2 600V 344 7574