3 Conductor

XL - XLTC - UNSHIELDED TRAY CABLE - 3 CONDUCTORS TYPE XHHW-2 WITH GROUND
Type XHHW-2: UL Type TC / TC-ER, 600 V, 90°C dry / wet rated - LEAD FREE
Insulation: Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-95-658
for XLPE insulation as standard. Sizes 14 AWG to 8 AWG are VW-1, and sizes 6 AWG and larger are non-VW-1.
Assembly: Conductors are cabled in concentric layers with interstices filled with suitable fillers, as required.  Ground wires, are sized
as required by UL 1277 (refer to the applicable product tables for the standard provided).  Sizes 14 AWG to 6 AWG have an insulated
green ground wire.  Sizes 4 AWG and larger have a bare ground wire.  A binder tape of synthetic material assembles the core in a tight circular configuration.
Jacket: UL listed sunlight and moisture resistant, sequentially length marked, black polyvinyl chloride (PVC) material meeting the requirements of UL 1277.

Bend Radius: 
5 x overall diameter installed (up to 2.0")
6 x overall diameter during installed (over 2.0")
8 x overall diameter during installation pull-in.

Notes:
• Dimensions and weights shown are nominal values.  They are subject to standard industry tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC 2008 and 
NEC 2011 Article 336.10(7).
• Ampacities are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) 
for conductors in a raceway or direct buried at 30°C ambient temperature and 90°C rated 
conductors.
• For correction factors for different ambient temperatures and ampacities at different conductor 
temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
(1) NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 
20 amperes for 12 AWG, and 30 AWG for 10 AWG copper conductors after any correction 
factors for ambient temperature and number of conductors have been applied.
Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G).

Scroll to add product to your quote.

Cole Number Size AWG No. Of Cond. JKT Wall Insul Wall NOM O.D. Ground AWG D.C. Volts AMPS (1) Weight LBS/MFT Color Quantity Add
16-0450 8 3 60 45 .665 10 600V 55 323
16-0452 6 3 60 45 .769 8 600V 75 451
16-0454 4 3 60 45 .818 8 600V 95 595
16-0456 2 3 80 45 .989 6 600V 130 922
16-0458 1 3 80 55 1.093 6 600V 150 1200
16-0460 1/0 3 80 55 1.181 6 600V 170 1358
16-0462 2/0 3 80 55 1.273 6 600V 195 1663
16-0464 3/0 3 80 55 1.405 4 600V 225 2156
16-0466 4/0 3 80 55 1.541 4 600V 260 2506
16-0468 250 3 80 65 1.634 4 600V 290 2941
16-0470 350 3 110 65 1.934 3 600V 350 4103
16-0472 500 3 110 65 2.190 2 600V 430 5670
16-0474 750 3 140 80 2.770 2/0 600V 520 9500