14AWG

Unshielded VNTC - UL Type TC or TC-ER, 600 V, 90°C dry and 75°C wet rated - LEAD FREE
Multiconductor 14 AWG Type THHN/THWN-2 
Insulation Thickness:  15 mils / 0.38mm PVC, 4 mils / 0.10mm Nylon Covering

Bend Radius:  5 x overall diameter installed / 8 x overall diameter during installation pull-in.

Notes:
• Dimensions and weights shown are nominal values, subject to standard industry tolerances.
• Cables with different conductor counts and bare or insulated grounds are are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in 
accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Table 310.15(B)(16) for  conductors in a raceway 
or direct buried at 30°C ambient temperature and 90°C rated conductors.  Ampacities for 
cables having more than three conductors have been derated per NEC Table 310.15(B)(3)(a).
•  For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different 
conductor temperature ratings see NEC Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 
14 AWG copper conductors after any correction factors for ambient temperature and 
number of conductors have been applied. Exceptions to this may be covered in 
NEC Article 240.4(E) through (G).
(1) Where the 4th conductor is the neutral of a balanced 3 phase system.
• Dimensions and weight are nominal and may vary
 

Colors

Conductor Identification:
• Per ICEA S-73-532-E3.4 Method 4
Conductors are black and numbered
• Per ICEA S-73-532-E3.1 Method 1 and Table E2 (formerly K2)
Colored Insulation (with stripe for 7th conductor and beyond)

Scroll to add product to your quote.

Cole Number Size AWG No. Of Cond. JKT Wall NOM O.D. D.C. Volts AMPS (1) Weight LBS/MFT Color Quantity Add
16-0050 14 2 45 .320 600V 25 64
16-0051 14 3 45 .345 600V 25 80
16-0052 14 4 45 .365 600V 20/25.1 96
16-0053 14 5 45 .397 600V 20 117
16-0054 14 6 45 .431 600V 20 137
16-0055 14 7 45 .431 600V 17.5 152
16-0056 14 8 45 .466 600V 17.5 175
16-0057 14 9 45 .502 600V 17.5 195
16-0058 14 10 60 .566 600V 12.5 232
16-0060 14 12 60 .591 600V 12.5 266
16-0063 14 15 60 .636 600V 12.5 326
16-0064 14 16 60 .653 600V 12.5 343
16-0067 14 19 60 .687 600V 12.5 396
16-0068 14 20 60 .707 600V 12.5 417
16-0070 14 25 60 .792 600V 11.3 518
16-0073 14 30 80 .886 600V 11.3 638
16-0075 14 37 80 .953 600V 10 774
16-0076 14 40 80 .988 600V 10 833
16-0077 14 50 80 1.083 600V 8.8 972